Part 1 - General
SUBMITTAL
Submit color samples for selection from manufacturer’s
group A, B, C, D or E. Submit product literature, certifications,
test reports and full-size sample(s) of each color specified.
QUALITY ASSURANCE
Certifications: All ground
face sound-absorbing masonry units shall be Trendstone®/Acousta-Wal®
units manufactured by Trenwyth Industries. Concrete blocks
shall conform to ASTM C90. The ground surfaces shall have
a factory-applied acrylic finish. Units shall conform to ASTM
C1262 with respect to freezing and thawing.
Production shall be monitored so that the top
of the units shall be completely closed and edges of slots
and ends of the blocks shall be straight and clean. Type IV
units shall have fillers, as supplied by Trenwyth Industries,
inserted in the cavities at the block plant. Type IV fillers
shall be fiberglass fillers laminated to metal septa. All
filler material shall be cut accurately to size and installed
as recommended for the type of Acousta-Wal units specified.
All units contain Trenwyth-approved integral water repellent
admixture at time of manufacture.
Trendstone/Acousta-Wal units shall have a tighter,
smoother face. Mold and moisture resistant, Trendstone/Acousta-Wal
units are graffiti resistant and easy to clean (never paint
or refinish). No VOC’s. Available in a wider color selection,
custom colors, and unique shapes and sizes, Trendstone/Acousta-Wal
units are ideal for interior and exterior applications. The
structural integrity of the unit results in a one-step, single
trade installation process. Trendstone/Acousta-Wal units are
distributed nationally.
Fire Resistance:
Define hourly ratings required as 1, 2, 3 or 4 hours.
Field Constructed Mock-ups:
Construct a sample panel, no less than 4' x 4', of units of
each color and size to be used in the project.
Trenwyth Industries requires ordering a full-size
unit to illustrate color and texture for approval.
Trenwyth Industries requires that a jobsite
sample panel be installed at the jobsite prior to installation
of any Trenwyth products. This panel will represent both the
quality of the product and the workmanship to be expected
for the project. The panel must be approved by either the
owner or the architect for the project. Trenwyth will provide
4" units for a 4' x 4' sample panel at no cost for the
material (not including freight to the site).
DELIVERY, STORAGE AND
HANDLING
Trendstone/Acousta-Wal units shall be delivered to
the jobsite on covered banded pallets with cardboard between
layers. Store pallets in single stacks on level ground and
cover with waterproof covering (e.g. tarpaulins) to protect
the blocks from inclement weather. Handle blocks carefully
to avoid breakage and damage to the finished surfaces.
PROJECT/SITE CONDITIONS:
Protection of Work: Cover
walls each day after installation to keep open walls protected
and dry. After units are installed, they should be protected
from damage by other trades performing operations that can
stain or otherwise damage the finished surfaces by covering
walls with plastic. Corners should be protected from damage
after installation by covering them with plywood.
Part II – Products
PRODUCT NAME
Trendstone®/Acousta-Wal® ground face sound-absorbing
masonry units
MANUFACTURER
Trenwyth Industries
One Connelly Road
Emigsville, PA 17318
(800) 233-1924
Trenwyth Industries
3400 E. Bungalow Road
Morris, IL 60450
(800) 358-3003
Trenwyth Industries
4626 N. 42nd. Ave
Phoenix, AZ 850019
(800) 331-9823
RELATED MATERIALS
Colored matching or contrasting mortar is available
at Trenwyth Industries. Consult NCMA TEK Notes, available
at www.trenwyth.com, for mortar type and specifications. For
all exterior mortar, use matching Trenwyth-approved water
repellent mortar additive, following manufacturer’s
instructions. Consult manufacturer for recommendations.
SIZES AND SHAPES
Acousta-Wal units surfaces are manufactured to provide
finished dimensions of 7-5/8" x 15-5/8" ±
1/8". Bed depth dimensions for single face units are
3-9/16", 5-9/16", 7-9/16", 11-9/16" ±
1/8". Two face units are 3-1/2", 5-1/2", 7-1/2",
11-1/2" ± 1/8". They shall be:
• |
4" or 6" thickness |
Type I |
• |
4" or 6" thickness |
Type IV |
• |
8", 10", or 12" thickness |
Type IRF |
• |
8", 10", or 12" thickness |
Type IVRF |
MASONRY CLEANERS
Use Burnished Custom Masonry Cleaner by PROSOCO (dilute one
part to 3 parts clean
water), carefully following manufacturer’s instructions.
Available at Trenwyth Industries. Do not powerwash.
Caution!
Never use Muriatic Acid solutions on units.
Part 3 -- Execution
LAYING MASONRY WALLS
Draw blocks from more than one pallet at a time during
installation. All exterior mortar shall include Trenwyth-approved
water repellent additive added to each batch in the appropriate
dosage rates for mortar type (M, S or N) per manufacturer’s
instructions. Refer to NCMA TEK Notes, available at www.trenwyth.com,
for Hot and Cold weather construction practices.
Trendstone/Acousta-Wal units shall be installed
by the general contractor or masonry contractor. Trendstone/Acousta-Wal
blocks shall be laid in running bond or stack bond as specified
with the closed tops up. The slots shall
face toward the room or area where sound absorption is required
as shown on the plans. Units shall be laid in a full horizontal
bed of mortar.
Lay units using the best concrete masonry practices.
Install only quality units; reject all defective units as
defined by ASTM C90. Lay blocks with the faces level, plumb
and true to the line strung horizontally at the ground face.
Units shall have uniform, 3/8"-wide joints both horizontally
and vertically on the finished side of the wall. Tool joints
neatly after they are finger-hard to make them straight and
uniform. Size and place cut pieces appropriately to maintain
consistency and bond. Slots shall be kept free of mortar and
debris and the exposed mortar at the bottom of each slot shall
be neatly tools. NO RAKE JOINTS.
INSTALLATION
Lighting: Provide adequate
lighting for masonry work by placing all lighting at a reasonable
distance from the wall for even illumination. Do not use trough
lighting.
Cutting: Make
all unit cuts, including those for bonding, holes, boxes,
etc., with motor-driven masonry saws using either an abrasive
or diamond blade. Cut neatly and locate for best appearance.
MORTAR BEDDING AND JOINTING
In all exterior mortar, we recommend using an approved
water repellent additive (which may be purchased from Trenwyth
Industries), following manufacturer’s instructions.
Consult manufacturer for recommendations.
FLASHING OF MASONRY WORK
Install flashing at locations shown in the plans and
in strict accordance with the details and the best masonry
flashing practices.
WEEP HOLES AND VENTS
Install weep holes and vents at proper intervals at
courses above grade and at any water stops over windows, doors
and beams. Consult NCMA TEK Notes, available at www.trenwyth.com,
for proper flashing and drawings.
INSPECTION
The ground faces shall conform to the requirements
of ASTM C90 when viewed from a distance of twenty (20) feet
at right angles to the wall with normal lighting.
CLEANING:
Keep walls clean daily during installation using brushes,
rags and the burlap squares supplied on the Trendstone/Acousta-Wal
pallet. Do not allow excess mortar lumps or smears to harden
on the finished surfaces. Harsh cleaning methods after walls
have been erected may mar the surface of the blocks.
FINAL CLEANDOWN
Clean the completed walls with PROSOCO Burnished Custom
Masonry Cleaner (dilute 1 part to 3 parts clean water), strictly following the manufacturer's
instructions – including thorough rinsing. Do not use
acid or abrasives on the finished surfaces. Failure to strictly
follow manufacturer's instructions can result in permanent
damage to the finished faces. Do not apply Burnished Custom
Masonry Cleaner with pressure spray above 50 psi. Do
not powerwash.
FIELD COAT APPLICATION
For completely finished walls, a finish coat of TRENDCOAT®
Acrylic (minimum 20% solids content) or TRENDCOAT® WB
(water-base) is recommended. Apply to all Trendstone/Acousta-Wal
walls after cleandown and when the walls are dry. Apply the
acrylic evenly to cover the entire surface without forming
drips or runs. For maximum coverage and best appearance, apply
TRENDCOAT Acrylic or TRENDCOAT WB with airless spray equipment.
Consult Trenwyth Industries for further information. This
clear, high-solids acrylic offers excellent graffiti resistance,
provides moisture resistance and helps to cover any scuffs
or scratches that may occur during handling and/or installation.
MAINTENANCE
Trendstone/Acousta-Wal units, properly installed and
cleaned, need virtually no maintenance other than routine
cleaning (i.e. Pinesol or Fantastik). Graffiti, paint or dye
stains may need special cleaning methods and products such
as Trenwyth’s Graffiti Wizard® environmentally friendly
cleaner. Contact manufacturer for specific cleaning recommendations.
INSTALLATION RECOMMENDATIONS
To ensure optimal sound-reduction performance:
- The unslotted side of Trendstone/Acousta-Wal blocks must
be painted or parged to seal the porosity of the aggregates.
- The units must be laid in a full horizontal bed of mortar.
They should be laid with the closed tops up.
- The slots should face toward the noise source (with the
exception of partitioning a small office off from a large
noisy plant area). Slots must be kept free of mortar. The
exposed mortar at the bottom of each slot should be neatly
tooled and all debris removed. NO RAKE JOINTS unless
tuckpointing with epoxy.
- Under no circumstances should the units be laid upside
down; that is, with the closed tops down. First, it would
be impossible to lay the units in a full horizontal bed
of mortar if they are laid upside down. Second, excess mortar
would fall into the slots giving an unsightly appearance.
If the cavity volume were reduced by more than 5 to 10%
due to mortar falling inside, the acoustical performance
of the units would be altered.
- For best appearance, use stack bond construction when
stack bond appearance is desired (as opposed to scored units
in running bond).
- A complementary or matching mortar color is recommended
when using Trendstone/Acousta-Wal units.
LIMITATIONS
- The facing is not intended for use as an impervious surface.
- Acid solutions or HCL-based cleaners should not be used
as a cleaning agent or in direct contact with the facing.
- The facing should not be continuously exposed to temperatures
above 250º F.
|