For the specifications of an
individual product line, please select the product below:
Astra-Glaze-SW+® | Verastone®
| Trendstone®
| Grey
Block
SPECIFICATIONS
– Printable : PDF
Version – Word
Version
Part 1 - General
SUBMITTAL
Submit color samples for selection from manufacturer’s
series. Submit product literature, certifications, test reports
and full-size sample(s) of each color specified or selected.
Custom colors are available. Contact Trenwyth for details.
QUALITY ASSURANCE
Certifications: All glazed sound-absorbing
masonry units shall be Astra-Glaze-SW+®/Acousta-Wal®
units manufactured by Trenwyth Industries. Glazed concrete
blocks manufactured in Pennsylvania shall be lightweight units
conforming to ASTM C90. Glazed concrete blocks manufactured
in Arizona shall be medium-weight units conforming to ASTM
C90 and all applicable Federal Specifications.
Mold and moisture resistant, Astra-Glaze-SW+/Acousta-Wal
units are USDA approved for sanitary and clean room environments.
The glazed facing is graffiti resistant and easy to clean
(never paint or refinish). No VOC’s. Available in custom
colors and unique shapes and sizes, Astra-Glaze-SW+/Acousta-Wal
units are ideal for interior and exterior applications. The
structural integrity of the backing (conforming to ASTM C90)
results in a one-step, single trade installation process.
Upon request, Trenwyth will manufacture Astra-Glaze-SW+/Acousta-Wal
with post-consumer recycled material. Contact Trenwyth Industries
for recycled content details.
Production shall be monitored so that the top
of the units are completely closed and edges of slots and
ends of blocks are straight and clean. Type IV units shall
have fillers, as supplied by Trenwyth Industries, inserted
in the cavities at the block plant. Type IV fillers shall
be fiberglass fillers laminated to metal septa. All filler
material shall be cut accurately to size and installed as
recommended for the type of Astra-Glaze-SW+/Acousta-Wal units
specified. All units contain Trenwyth-approved integral water
repellent admixture at time of manufacture.
Fire Resistance:
Define hourly ratings required as 1, 2, 3 or 4 hours.
Field Constructed Mock-ups:
Construct a sample panel, no less than 4' x 4', of each color
and size to be used in the project.
Trenwyth Industries requires ordering a full-size
unit to illustrate color and texture for approval.
Trenwyth Industries requires a jobsite sample
panel be installed at the jobsite prior to installation of
any Trenwyth products. This panel will represent both the
quality of the product and the workmanship to be expected
for the project. The panel must be approved by either the
owner or the architect for the project. Trenwyth will provide
4" Astra-Glaze-SW+/Acousta-Wal units for a 4' x 4' sample
panel at no cost for the material (not including freight to
the site).
DELIVERY, STORAGE AND
HANDLING
Astra-Glaze-SW+/Acousta-Wal glazed sound-absorbing
units shall be delivered to the jobsite on banded pallets
with individual protective covers on each glazed sound-absorbing
block face. Keep protective block covers on the blocks until
installation. Store pallets in single stacks on level ground
and cover with waterproof covering (e.g. tarpaulins) to protect
the blocks from inclement weather. Handle blocks carefully
to avoid breakage and damage to the finished surfaces.
PROJECT/SITE CONDITIONS:
Protection of Work: Cover
walls each day after installation to keep open walls protected
and dry. After units are installed, they should be protected
from damage by other trades performing operations that can
stain or otherwise damage the finished surfaces by covering
walls with plastic. Corners should be protected from damage
after installation by covering them with plywood.
Part II – Products
PRODUCT NAME
Astra-Glaze-SW+®/Acousta-Wal® glazed sound-absorbing
masonry units
MANUFACTURER
Trenwyth Industries
One Connelly Road
Emigsville, PA 17318
(800) 233-1924
Trenwyth Industries
4626 N. 42nd Avenue
Phoenix, AZ 85019
(800) 331-9823
RELATED MATERIALS
Colored matching or contrasting mortar is available
at Trenwyth Industries. Consult NCMA TEK Notes, available
at www.trenwyth.com, for mortar type and specifications. For
all exterior mortar, use matching Trenwyth-approved water
repellent mortar additive, following manufacturer’s
instructions. Consult manufacturer for recommendations.
In areas that are exposed to excessive moisture,
we recommend joints to be raked and filled with BONSAL B-7000
EPOXY. See Mortar Bedding and Jointing for details.
SIZES AND SHAPES
Actual facing dimensions shall be 7-3/4" x 15-3/4"
forming a 1/16" lip around the edges of a modular 7-5/8"
x 15-5/8" block. Nominal 2", 4", 6", 8"
10" and 12" standard block thickness shall be used
as required, as well as standard and special block shapes.
Basic units may include stretchers, jambs, caps and cove bases.
• |
4" or 6" thickness |
Type I |
• |
4" or 6" thickness |
Type IV |
• |
8", 10", or 12" thickness |
Type IRF |
• |
8", 10", or 12" thickness |
Type IVRF |
MASONRY CLEANERS
Use Custom Burnished Masonry Cleaner by PROSOCO (dilute
1 part to 3 parts clean water), carefully following manufacturer’s
instructions. Available at Trenwyth. Do not powerwash.
Caution! The
following solvents must never be used as they may damage the
Astra-Glaze-SW+/Acousta-Wal block facings: paint remover,
lacquer thinner, epoxy thinner, methylene chloride acetone,
muriatic acid. Contact Trenwyth Industries for recommendations
for hard to clean areas.
Part 3 — Execution
LAYING MASONRY WALLS
Draw blocks from more than one pallet at a time during installation.
All exterior mortar shall include Trenwyth-approved water
repellent additive added to each batch in the appropriate
dosage rates for mortar type (M, S or N) per manufacturer’s
instructions. Refer to NCMA TEK Notes, available at www.trenwyth.com,
for Hot and Cold weather construction practices.
Astra-Glaze-SW+/Acousta-Wal units shall be installed
by the general contractor or masonry contractor using the
best concrete masonry practices. Astra-Glaze-SW+/Acousta-Wal
blocks shall be laid in running bond or stack bond as specified
with the closed tops up. The slots shall
face toward the room or area where sound absorption is required
as shown on the plans. Units shall be laid in a full horizontal
bed of mortar.
Lay units using the best concrete masonry practices.
Install only quality units; reject all defective units as
defined by ASTM C744. Lay Astra-Glaze-SW+/Acousta-Wal with
the faces level, plumb and true to the line strung horizontally
at the glazed face. Units shall have uniform face joint dimensions
of 1/4" both horizontally and vertically. Tool joints
neatly after they are finger-hard to make them straight and
uniform. Size and place cut pieces appropriately to maintain
consistency and bond. Slots shall be kept free of mortar and
debris and the exposed mortar at the bottom of each slot shall
be neatly tooled. NO RAKE JOINTS unless tuckpointing
with epoxy.
INSTALLATION
Lighting: Provide adequate
lighting for masonry work by placing all lighting at a reasonable
distance from the wall for even illumination. Do not use trough
lighting.
Base Course: Align
base course properly on the floor slab.
Cove Base: Keep
the cove base tight to the slab if vinyl floor tile is to
be installed. For thicker flooring, raise cove base units
to the desired height.
Cutting: Make
all unit costs, including those for bonding, holes, boxes,
etc., with motor-driven masonry saws using either an abrasive
or diamond blade. Cut neatly and locate for best appearance.
MORTAR BEDDING AND JOINTING
- Lay units with full mortar coverage on head and bed joints
taking care not to block cores to be grouted or filled with
masonry insulation.
- Tool all mortar joints when thumbprint hard into a concave
configuration.
- Care should be taken to remove mortar from the face of
masonry units before it sets.
- Tuckpoint the joints of scored units for proper appearance.
All exterior scored units must be tuckpointed to prevent
water penetration. Rake back the joint when epoxy (Bonsal/Laticrete)
is used on select jobs that require better moisture prevention.
Various masonry mortars may be used with Astra-Glaze-SW+/Acousta-Wal
concrete masonry units depending on specific structural requirements
for the finished walls. In all exterior mortar, we recommend
using the matching Trenwyth-approved water repellent mortar
additive (which may be purchased at Trenwyth Industries),
following manufacturer’s instructions. Consult manufacturer
for recommendations.
EPOXY FINISHED JOINTS
In areas exposed to excessive moisture, make sure to
tool mortar joints with a minimum of 1/4" and tuckpoint
with an approved water-resistant grout. A typical tuckpointing
grout is BONSAL® POLYMER MODIFIED SANDED TILE GROUT mixed
with the BONSAL B-7000 EPOXY. Do not add water or anything
else in addition to the B-7000, which will make it a 100%
solid enabling it to be acid and stain resistant.
Recommendations for using BONSAL®
– DO NOT FLOAT GROUT ACROSS GLAZED SURFACE. THE PROPER
TECHNIQUE IS TO POINT OR USE A MORTAR GUN!
FLASHING OF MASONRY WORK
Install flashing at locations shown in the plans and
in strict accordance with the details and the best masonry
flashing practices.
WEEP HOLES AND VENTS
Install weep holes and vents at proper intervals at
courses above grade and at any water stops over windows, doors
and beams. Consult NCMA TEK Notes, available at www.trenwyth.com,
for additional information on flashing.
INSPECTION
The glazed facing shall conform to the requirements
of ASTM C744 when viewed from a distance of five (5) feet
at right angles to the wall with normal lighting. The concrete
masonry units on which the glaze is molded shall conform to
the requirements
of ASTM C90.
CLEANING:
Keep walls clean daily during installation using brushes
or rags and a clean damp cloth. Harsh cleaning methods after
walls have been erected may mar the surface of the blocks.
Do not allow excess mortar lumps or smears to harden on the
glazed surfaces. Remove green mortar with a dry cloth. Do
not use steel wood, sandpaper or other abrasives.
FINAL CLEANDOWN
Clean the completed walls with Burnished Custom Masonry
Cleaner by PROSOCO (dilute 1 part to 3 parts clean water),
carefully following manufacturer’s washdown instructions
— including thorough rinsing. Do not use acid or abrasives
on the glazed surfaces.
MAINTENANCE
Astra-Glaze-SW+/Acousta-Wal units, properly installed
and cleaned, need virtually no maintenance other than routine
cleaning with standard commercial grade cleaning agents such
as PINESOL® or Fantastik®. Graffiti, paint or dye
stains may need special cleaning methods and products, such
as Trenwyth’s Graffiti Wizard® environmentally friendly
cleaner. Contact manufacturer for specific cleaning recommendations.
INSTALLATION RECOMMENDATIONS
To ensure optimal sound-reduction performance:
- The unslotted side of Astra-Glaze-SW+/Acousta-Wal blocks
must be painted or parged to seal the porosity of the aggregates.
- The units must be laid in a full horizontal bed of mortar.
They should be laid with the closed tops up.
- The slots should face toward the noise source (with the
exception of partitioning a small office off from a large
noisy plant area). Slots must be kept free of mortar. The
exposed mortar at the bottom of each slot should be neatly
tooled and all debris removed. NO RAKE JOINTS unless
tuckpointing with epoxy.
- Under no circumstances should the units be laid upside
down; that is, with the closed tops down. First, it would
be impossible to lay the units in a full horizontal bed
of mortar if they are laid upside down; and, second, excess
mortar would fall into the slots giving an unsightly appearance.
If the cavity volume were reduced by more that 5 to 10%
due to mortar falling inside, the acoustical performance
of the units would be altered.
GENERAL INSTALLATION RECOMMENDATIONS:
- For walls with a glazed finish on both sides, use two
single-faced units. Because masonry units are typically
installed aligning one side, the second side of double faced
units is almost invariably misaligned. Double-faced units
are not recommended. Trenwyth accepts no responsibility
for face alignment.
- For best appearance, use stack bond construction when
stack bond appearance is desired (as opposed to scored units
in running bond).
- All exterior mortar joints must contain a Trenwyth-approved
water repellent mortar additive, carefully following manufacturer’s
instructions.
- For best appearance and water resistance, tuckpoint scored
joints on interior and exterior applications.
- Colored matching or contrasting mortar / epoxy is available
when using colorful Astra-Glaze-SW+/Acousta-Wal units. Contact
Trenwyth Industries for information.
|